Permit Number: T09BU01803
Parcel: 13303300A

Review Status: Completed

Review Details: POOL/SPA

Permit Number - T09BU01803
Review Name: POOL/SPA
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2009 JASON GREEN ENGINEERING REVIEW Approved
12/09/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the water flow to the solar water heater will be balanced with the pool filter flow.
12/09/2009 TERRY STEVENS ZONING REVIEW Approved
12/09/2009 DAVE MANN FIRE REVIEW Approved
12/09/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the termination of the vent pipes in the pool equipment room.
2. Indicate the maximum vent line length required to achieve suction cut-off within 3 seconds.
12/10/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/10/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved