Permit Review Detail
Review Status: Completed
Review Details: POOL/SPA
Permit Number - T09BU01803
Review Name: POOL/SPA
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/09/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 12/09/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the water flow to the solar water heater will be balanced with the pool filter flow. |
| 12/09/2009 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 12/09/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/09/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the termination of the vent pipes in the pool equipment room. 2. Indicate the maximum vent line length required to achieve suction cut-off within 3 seconds. |
| 12/10/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/10/2009 | RICHARD JIROUDEK | ELECTRICAL-COMMERCIAL | REVIEW | Approved |