Permit Number: T09BU01057
Parcel: 13316027S

Address:
2050 N WILMOT RD

Review Status: Completed

Review Details: GRADING

Permit Number - T09BU01057
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2009 ANDREW CONNOR ZONING REVIEW Denied August 31, 2009

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T09BU01057 Grading Plans for S08-???

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved tentative plat. Please submit one copy of the CDRC approved and stamped tentative plat, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the CDRC approved and stamped tentative plat. Additional comments may be forthcoming.
08/12/2009 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the COT approved plan including landscape and native plant preservation plans for reference. Revise grading plans as necessary to comply with the approved documents.
08/25/2009 LOREN MAKUS ENGINEERING REVIEW Denied August 27, 2009
T09BU01057

1. Clarify the status of the lot. Currently the areas labeled as Block 1 and Block 2 are still a single lot. Indicate that the boundaries shown are proposed until the plat is approved and recorded.
2. Include the drainage report with the grading plan submittal. Include a discussion showing how the differences between the proposed drainage and the previously approved drainage designs are justified.
3. Clearly show the locations and quantities of on-site and off-site discharges that affect the site. Clearly show off-site contours to the extent that they affect drainage onto and from the project site.
4. Ensure that data is not overlapped to render it illegible.
5. Clearly show and provide details for all inlet and outlet structures both existing and proposed. Provide sufficient detail to show how drainage is currently discharged from the site and how proposed changes will be made.
6. Correct the section callouts to refer to the correct sheets.
7. Clarify the extent of work that is proposed for this grading permit.
8. Provide a legend to identify all symbols used on the plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/03/2009 SUE REEVES OUT TO CUSTOMER Completed
09/03/2009 SUE REEVES REJECT SHELF Completed