Permit Number: T09BU00284
Parcel: 20564072C

Review Status: Completed

Review Details: RESUBMITTAL - SWPPP

Permit Number - T09BU00284
Review Name: RESUBMITTAL - SWPPP
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2010 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 03/31/2010

Mountain Vail Estates, Part F, Lots 323 thru 338 and 346 thru 384 and Common Area "B" Grading Plan Comments:

1- The Geotechnical Report shall recommend the required setback from existing/proposed slopes whether they are created by a cut or a fill. Verify compliance with the Soils Report recommendation.
2- Provide construction and access easement to install part of Chevrolet Drive and use it for access on the adjacent property near Lots 379 and 323. Explain when and how the easement will be provided.
3- Is B-7 access ramp slope 12:1 or 18:1? Revise as needed.

SWPPP Comments:

1. Show on the SWPPP exhibit possible locations for on-site waste storage or receptacles, borrow areas, or other supporting activities (Part III.C.3.e).

If you have any questions, Laith Alshami may be reached at 837-4933 or Laith.Alshami@tucsonaz.gov