Permit Number: T09BU00284
Parcel: 20564072C

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T09BU00284
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2010 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 03/31/2010

Mountain Vail Estates, Part F, Lots 323 thru 338 and 346 thru 384 and Common Area "B" Grading Plan Comments:

1- The Geotechnical Report shall recommend the required setback from existing/proposed slopes whether they are created by a cut or a fill. Verify compliance with the Soils Report recommendation.
2- Provide construction and access easement to install part of Chevrolet Drive and use it for access on the adjacent property near Lots 379 and 323. Explain when and how the easement will be provided.
3- Is B-7 access ramp slope 12:1 or 18:1? Revise as needed.

SWPPP Comments:

1. Show on the SWPPP exhibit possible locations for on-site waste storage or receptacles, borrow areas, or other supporting activities (Part III.C.3.e).

If you have any questions, Laith Alshami may be reached at 837-4933 or Laith.Alshami@tucsonaz.gov
04/05/2010 ANDREW CONNOR ZONING REVIEW Denied 03/30/2010

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan at this time.

2. While zoning acknowledges that the grading plan is in substantial zoning compliance as it relates to the Zoning review purview, with the approved version of the tentative plat, the grading plan cannot be approved at this time. Prior to Zoning approval the Engineering and Landscape Sections must approve the grading plan.
04/05/2010 ANDREW CONNOR NPPO REVIEW Denied Ensure that all Engineering comments and concerns are addressed prior NPP / Landscape approval stamp.