Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09BU00282
Parcel: 20564072C

Review Status: Completed

Review Details: RESUBMITTAL - SWPPP

Permit Number - T09BU00282
Review Name: RESUBMITTAL - SWPPP
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2010 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 03/30/2010

Mountain Vail Estates, Part D, Lots 216 thru 242 and 287 thru 322, C.A. "B" Grading Plan Comments:

1- The Geotechnical Report shall recommend the required setback from existing/proposed slopes whether they are created by a cut or a fill. Verify compliance with the Soils Report recommendation.
2- Provide construction easement to work on the adjacent property near Lots 272 thru 286 wherever applicable. Clarify how the easements will be provided.

SWPPP Comments:

1. Show on the SWPPP exhibit possible locations for on-site waste storage or receptacles, borrow areas, or other supporting activities (Part III.C.3.e).

If you have any questions, Laith Alshami may be reached at 837-4933 or Laith.Alshami@tucsonaz.gov