Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SWPPP
Permit Number - T09BU00279
Review Name: RESUBMITTAL - SWPPP
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/21/2011 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 01/24/2011 Mountain Vail Estates, C.A. "B" - Drainage, Recreational & Landscaped Area and C.A. "C"- Esmond Station Rail Line and Trail Grading Plan Comments: 1- Cloud all proposed revisions to facilitate the review. 2- It does not appear that Keynote #6 is applicable. Remove the note and revise as necessary. 3- The area north of Basin B-13 does not appear to the basin according to the provided grades. Provide additional grades to clarify the proposed drainage pattern. 4- Draw in the missing part of the trail described in Keynote #15. SWPPP Comments: 1. It appears that the proposed revision can be addressed in the field pertaining to the approved SWPPP. If you have any questions, Laith Alshami may be reached at 837-4933 or Laith.Alshami@tucsonaz.gov |