Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SWPPP
Permit Number - T09BU00278
Review Name: RESUBMITTAL - SWPPP
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/22/2010 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 03/29/2010 Mountain Vail Estates, Part A, Lots 1 thru 135 Grading Plan Comments: 1- The Geotechnical Report shall recommend the required setback from existing/proposed slopes whether they are created by a cut or a fill. Verify compliance with the Soils Report recommendation. 2- Provide the sediment trap elevations on Details #2/2, 4/2 1/5, 2/5 and 3/5. 3- It is not clear why Detail 5/5 was added. Clarify the need for all three details (i.e. 1 /4, 2/4 and 5/5. 4- Show a typical cross section detail for the proposed retaining wall between lots 64-66 and between Lot 82 and Basin B-1. The response to this comment is not clear. 5- Clarify if the spillway in Detail 2/6 should have a slope. Detail 2/6 does not show a slope. 6- Proposed streets profiles sheets were not included in the previous submittal. It does not appear that the new 12 sheets review fee was paid. The fee must be paid before the new sheets can be reviewed. 7- Clarify where Keynote #10 callout is located on Sheet 5 of 7. The response does not appear to answer this comment. 8- Call out any bollards at the end of Creosote Range Drive, north of Basin B-4. The answer to this comment states that Creosote Range Drive is access to locale residence. Clarify how this section of the is used as access. SWPPP Comments: 1. Show possible locations for stockpiling and waste storage areas on the exhibit. If you have any questions, Laith Alshami may be reached at 837-4933 or Laith.Alshami@tucsonaz.gov |