Plan Number: T08PI00016
Parcel: Unknown

Address:
5145 S 1ST AV

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T08PI00016
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2008 SMONTIE1 UTILITY CLEARANCES COT STREETS DIVISION Completed
05/27/2008 SMONTIE1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
05/27/2008 SMONTIE1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
05/27/2008 SMONTIE1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
05/27/2008 SMONTIE1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
05/27/2008 SMONTIE1 UTILITY CLEARANCES COX COMMUNICATION Completed
05/27/2008 SMONTIE1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
05/27/2008 SMONTIE1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
05/27/2008 SMONTIE1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
06/02/2008 GARY WITTWER DOT LANDSCAPE REVIEW Approved
06/03/2008 RICHARD LEIGH DOT ENGINEERING REVIEW Approv-Cond April 16, 2008

SUBJECT: Park Avenue Improvements, Sunnyside Pointe, PIA T08PI0016, I-2008-017

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and recommends tentative approval of the PIA Plan set. The following comments need to be addressed prior to submittal of the mylar plan set for final review.

1. Lighten shading used for new pavement.

2. A full/"Type A" curb access ramp will have to be provided at Sta. +/- 80+75, RT. (Park Avenue) to connect the existing sidewalk leading into the Park Village Apartments.

Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsoz.gov
06/13/2008 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
06/19/2008 JOSE ORTIZ DOT TRAFFIC REVIEW Approv-Cond Remove left turn arrow legends from plans.
06/20/2008 SMONTIE1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
06/20/2008 SMONTIE1 PIA COORDINATOR OUT TO CUSTOMER Completed