Plan Number: T08PI00016
Parcel: Unknown

Address:
5145 S 1ST AV

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T08PI00016
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2008 SMONTIE1 UTILITY CLEARANCES COT STREETS DIVISION Denied Please submit utility clearance letters.
03/31/2008 SMONTIE1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied Please submit utility clearance letters.
03/31/2008 SMONTIE1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied Please submit utility clearance letters.
03/31/2008 SMONTIE1 UTILITY CLEARANCES QUEST COMMUNICATION Denied Please submit utility clearance letters.
03/31/2008 SMONTIE1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied Please submit utility clearance letters.
03/31/2008 SMONTIE1 UTILITY CLEARANCES COX COMMUNICATION Denied Please submit utility clearance letters.
03/31/2008 SMONTIE1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied Please submit utility clearance letters.
03/31/2008 SMONTIE1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied Please submit utility clearance letters.
03/31/2008 SMONTIE1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied Please submit utility clearance letters.
04/16/2008 RICHARD LEIGH DOT ENGINEERING REVIEW Denied April 16, 2008

SUBJECT: Park Avenue Improvements, Sunnyside Pointe , PIA T08PI0016. I-2008-017

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal.

1. Include the plan number "I-2008-017" in title block of each sheet.

2. Include Development Services Department PIA activity number (T0800016) on cover sheet.

3. Provide a dimensioned detail of each type of curb access ramp proposed in the plan set.

4. Lighten shading used for new pavement.

5. Show and label all existing roadway infrastructures (curb, sidewalk, access ramps, etc). Use differing line weights for existing and proposed and use symbols and abbreviations per PC/COT Standard. Details. 100 and 101.

6. Show existing curb openings and indicate that any abandoned curb openings along Park Avenue will be closed.

7. Provide a cross section of the proposed pavement widening on Park Avenue.

8. Locate sidewalk closer to curb, provide a 0 to 3' setback from curb. If necessary, the sidewalk may meanderer around any obstructions. Additionally, The minimum sidewalk width along a roadway listed on the Major Streets and Routes plan is 6'.

9. Add the following general Note:

The contractor shall contact and/or coordinate any work with COT Streets & Traffic Maintenance Division, Electric Shop (791-3154) prior to relocation or placement of any street lighting or traffic facilities. Please Contact Ernie Encinas at 520-791-3154 for street lighting/traffic signal plan review.

Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsoz.gov
04/21/2008 GARY WITTWER DOT LANDSCAPE REVIEW Denied Will the construction impact any of the vegetation on the west side. If so, please address the NPPO.
04/23/2008 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed this plan and have the following comments:

1. Sheet 1 - Note 3 - this note states that both mix #1 and mix #3 will be used in the paving. The pavement section only shows 2" AC over 10" ABC. What will be the pavement section?
2. Typically the City requires 6 foot wide sidewalk along major arterials. Please confirm that 5 foot sidewalk will be acceptable.
3. Will there be any landscaping installed with this project? If so, please submit the landscaping plan to Paul Rosenboom at 4004 S. Park Avenue Bld #2 for review.

No further comments.
04/25/2008 JOSE ORTIZ DOT TRAFFIC REVIEW Denied April 25, 2008
ACTIVITY NUMBER: T08PI00016
PROJECT NAME: Sunnyside Pointe-Park
PROJECT ADDRESS: 5145 S 1st Avenue
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal.

The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. See redlines on the submitted drawings and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.

3. The proposed right turn/decel lane is substandard therefore adjust the taper of the proposed right turn/decel lane to maximize queuing. See redlines for illustrations.

4. Install street names with the proposed R1-1 (Stop Sign) at the proposed roadway entering this development off of Alvernon Way per PCDOT & TDOT Signing Manual (2002) Chap 5-11, 5-12, and Chap 9-2.

5. Install a W14-2a (No Outlet) plaque beneath the street name signs along Alvernon Way.

6. Provide a 'RIGHT LANE' (R3-5F) supplemental plaque under the new (R3-5R) along Alvernon Way.

7. Place the PIA and CDRC Case number on the cover sheet.

8. Add the following Pavement Marking/Striping General Notes to the Plans:

'ALL NON-SIGNALIZED INTERSECTION STREET NAMES MUST HAVE E-W BLOCK NUMBER ADDRESSES FOR E-W ROADWAYS AND N-S BLOCK NUMBER ADDRESSES FOR N-S ROADWAYS.'



If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
04/28/2008 SMONTIE1 PIA COORDINATOR CUSTOMER CALLED Completed
04/28/2008 SMONTIE1 PIA COORDINATOR OUT TO CUSTOMER Completed