Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08EL00828
Parcel: 13311002S

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL00828
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08EL00828 5/9/08

1. For single dwelling calculation, the heating/ac load must be added after the 40% demand factor is taken. NEC 220.82.
2. Four units, not 8.
3. For service load calculation, the house panel must be added after the demand factor is taken. NEC 220.84.
4. For service calculation, the demand factor is 0.45, not 0.43. NEC 220.84.
5. Calculate neutral current per NEC 220.61, and show calculations.