Permit Number: T08CM03751
Parcel: 12305188B

Address:
2335 E ELM ST

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM03751
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2009 TERRY STEVENS ZONING REVIEW Approved
02/26/2009 GERRY KOZIOL WWM REVIEW Approved
03/02/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: March 2, 2009
SUBJECT: Site Plan, Building Plan
TO: Siri Trumble
LOCATION: 102 E Blacklidge Drive, T14S, R14E, Section 5, Ward 6
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T08CM3751

RESUBMITTAL REQUIRED: Building Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the building plan at this time. Please address the following review comments prior to the next submittal.

Please include:
1. A response letter to the comments along with the corrected copies of the Building Plan.
2. Cost estimate exceeds maximum allowable 50% improvement for substantial improvement. Revise cost estimate to separate material and labor. See example of cost estimate enclosed for minimum requirements (Logo, contractor's name, reference project address, etc).
3. If this is a historic home, please provide registration along with an explanation for the improvement.
4. Include Floodplain Use Permit with next submittal (Note that there is a $50.00 permit fee).
5. This property is located within a City of Tucson identified 100-year floodplain. Openings will be required in proposed wall to permit the entry and exit of flood waters. Openings should be a maximum of 10 foot on center.
6. Additional requirements may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
03/06/2009 THAUSER1 OUT TO CUSTOMER Completed