Permit Number: T08CM03746
Parcel: 11201020B

Address:
3974 N TUCSON BL

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T08CM03746
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2009 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T08CM03746
3974 N. Tucson Blvd.
Site Plan

TRANSMITTAL DATE: 03/19/09

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The following comments have not been addressed. DS 2-02.2.1.2 A search of Pima County records indicates there are seven tax parcels that constitute this site. A tax parcel lot combination will be required to create a single parcel. Provide a copy of the tax parcel combination for review.

Provide on the site plan the legal description of the parcel.

2. This comment has not been completely addressed. DS 2-02.2.1.4 On the location map provide the location of jurisdictional boundaries, and it does not appear that River Road and the Rillito River are indicated correctly. Revise.

3. This comment has not been completely addressed. DS 2-02.2.1.5 Provide lot dimensions and bearings.

4. DS 2-02.2.1.9 Provide a detail of the class two bicycle parking areas, including dimensions, type of rack, access aisle, surfacing materials, etc. See DS 2-09 for criteria.

This site is full code compliance, therefore the existing single pipe bicycle racks are not allowed and must be replaced.

5. This comment has not been completely addressed. DS 2-02.2.1.11 Clearly dimension the widths of all existing and proposed PAALs. Minimum width of a two way PAAL is 24'.

Provide wheel stop curbing or barriers to prevent vehicles from driving onto unimproved portions of this site. The header detail indicated on detail 2 sheet L-21 does not meet the minimum 6" above the paving in order to constitute a barrier.

The area indicated as "horse trailer parking" is considered a vehicle use area and is required to be paved, concrete or chip sealed. Decomposed granite does not meet this requirement. Provide wheel stop curbing or barriers to prevent vehicles from driving onto unimproved portions of this site in this area also.

6. This comment has not been completely addressed. DS 2-02.2.1.12 Provide a pedestrian circulation path to all proposed structures (ramadas) and to the proposed "horse trailer parking area".

Clearly indicate the minimum required sidewalk width of four (4) feet for the pedestrian circulation path.

7. All requested changes are to be made to all applicable sheets. Some changes have been made to sheet L-3 but have not been made to sheets L-5, L-6 nor to the landscape plans.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T08CM03746-2.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
03/19/2009 RONALD BROWN ADA REVIEW Denied 1. Comments 1 and 2: Changes are reflected on sheet L-3 only. All other drawings must show changes including large scale plans and civil drawings.
2. Ditto above concerning comment 3.
3. Comment 4: Grades provided on civil drawings are not sufficient to show accessible slope compliance as per section 4.3.7.
03/25/2009 ANDREW CONNOR LANDSCAPE REVIEW Approv-Cond Ensure that all changes requested by Zoning and Engineering divisions are re-submitted for review by landscape, re-stamp may be required.
03/25/2009 ANDREW CONNOR NPPO REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2009 CPIERCE1 OUT TO CUSTOMER Completed
04/08/2009 SUE REEVES REJECT SHELF Completed