Permit Number: T08CM03746
Parcel: 11201020B

Address:
3974 N TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM03746
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/06/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/06/2009 ROBERT SHERRY WATER REVIEW Approved
01/07/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: Rio Vista Park Improvements
3947 N Tucson Blvd
T08CM03746

The Pre-Manufactured Restroom Building shown on sheet E-1 has a 100 amp panel inside, this panel appears to feed fixtures and or equipment inside the Restroom Building. Would you provide information on this pre-manufactured building regarding the electrical wiring and equipment it feeds. Would this be a type of Listed or Approved Building ?


Ray T Majuta
Electrical Plan Check
DSD City of Tucson
520-837-4988
1-07-09
12/22/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide a defferred submittal to Building Official for the following:
a. Three Ramada Structures
b. One Modular Toilet Structure
c. One Playgeound Fabric Structure
d. One Sail Structure
12/22/2008 RONALD BROWN ZONING HC SITE REVIEW Passed
12/23/2008 TERRY STEVENS ZONING REVIEW Denied 12/23/2008

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
12/23/2008 MARTIN BROWN FIRE REVIEW Approved
12/23/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/26/2008 GERRY KOZIOL WWM REVIEW Denied NEED PLUMBING DRAWING FOR COMFORT STATION FOR SEWER CONNECTION FEE CALCUATIONS
APPROVED FOR 4" CONNECTION TO 8" PUBLIC (C-2)- NEED PCRWRD 3RD FLOOR REVIEW- KAREN SANSON/740-6369 (WORK IS IN VICINITY OF NUMEROUS LARGE PUBLIC SEWER TRUNK LINES- EXTREME CARE MAY BE NEEDED TO TAP 8" PUBLIC SEWER WITH 4" HCS)

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2009 THAUSER1 OUT TO CUSTOMER Completed
01/12/2009 SUE REEVES REJECT SHELF Completed