Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03630
Parcel: 140430130

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM03630
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2008 MARTIN BROWN FIRE REVIEW Denied Fire Department requires fire sprinklers under canopy
11/24/2008 ROBERT SHERRY WATER REVIEW Approved
11/24/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/24/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
11/24/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the termination of the secondary roof drains (ORWL). The discharge shall be above grade in a location that is observable to the building occupants and maintenance personnel. Reference: Section 1101.11.2.2.1, UPC 2006.
11/25/2008 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
11/25/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. 1/8" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL FOR 3/32" LETTERING IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY THE DRAWINGS SUBMITTED FOR CHECKING.
2. DEFERRED SUBMITTALS REQUIRE A WRITTEN APPROVAL BY THE BUILDING OFFICIAL, JESSIE SANDERS.
3. SHEET S1.2; DETAIL T1: PROVIDE CALCULATIONS FOR DECK DIAPHRAGM CONNECTION REQUIREMENTS.
4. SHEET S3.1; DETAIL 206: THE CONNECTION BETWEEN THE CAP PLATE AND THE STEEL BEAM IS NOT ANCHOR BOLTS. CLARIFY.
5. SHEET S3.1: REVISE DETAIL 102 ON THE DRAWINGS TO REFLECT CHANGES PER SK1.
6. STRUCTURAL CALCULATIONS SHEET 1: PROVIDE STRENGTH OF CONCRETE FOR APPLICATIONS OTHER THAN FOUNDATIONS.
7. STRUCTURAL CALCULATIONS SHEET 1: PROVIDE SOILS REPORT THAT IS REFERENCED.
11/25/2008 RONALD BROWN ZONING HC SITE REVIEW Passed Court yard is existing, accessibility features are existing, new canopy only.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/25/2008 CPIERCE1 OUT TO CUSTOMER Completed