Permit Number: T08CM03614
Parcel: 136092090

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03614
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Literature presented for the pole mounted lighting fixture is not a specification guide. These are installation and assembly instructions. We need to know height of pole, operating characteristics of the lamp and fixture and how it complies with the Outdoor Lighting Code; actual catalog cuts of the fixture.
2. Please provide a pole foundation detail. If the pole is 20' or higher, structural calculations are required.

END OF REVIEW
09/17/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied Per the Final Plat, Basketball court appears to be located within identified NUOS area. All zoning and landscaping comments must be addressed and plans approved prior to engineering approval.
09/21/2009 DAVID RIVERA ZONING REVIEW Denied Building approval required for the lighting prior to zoning approval.
09/28/2009 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied Previous comment #1 not addressed. Will need a plan for electric to show circuits, locations, methods of installation, details for poles, disconnecting means, and load calculations.

Previous comment #2 not addressed. Calclulations given are incomplete. How many acres is the lot? How many lumens allowed (12,000 x acres)? Show locations of all existing and new lighting.

Previous comment #3 not addressed. Please transfer your cut sheet to plan sheets. You must provide informaition for depth of footing, diamieter of footing, height of pole, etc. Mimimum font size for plans is 3/32" so if you use cut sheets they must be enlarged onto plan pages.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2009 CPIERCE1 OUT TO CUSTOMER Completed
10/08/2009 SUE REEVES REJECT SHELF Completed