Permit Number: T08CM03614
Parcel: 136092090

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM03614
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied REFERENCE ZONING COMMENTS CONCERNIING INACCURATE DOCUMENTS
01/21/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/29/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DSD TRANSMITTAL

FROM: Bianca Ramirez
Engineering Department

PROJECT: T08CM03614
2335 S Reflection Vista
Building Plan

TRANSMITTAL DATE: 1-29-09

COMMENTS: Please resubmit revised drawings a response letter, which states how all Engineering Review Section comments regarding Development Standards have been addressed with next submittal.

1. Unable to approve building plan until all site plan comments have been addressed.
2. Proposed Sport Court is located within Natural Undesturbed Open Space (NUOS) - no disturbance is permitted within this area. Revise so that no distubance is taking place within NUOS.
3. Engineering cannot approve permit(s) until all zoning comments have been addressed.
4. Additional comments may be forthcoming.


If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
02/09/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T08CM03614
2335 S Reflection Vista
Sport Court

Electrical plan denied for the following,
1.Provide information on how the light will be fed, where will it be fed from, wiring method to be used, switch or disconnect ?
2. The current City of Tucson/Pima county Outdoor Lighting will hace to be reviewed in order to comply with lumens allowed per site and any other requirements.
3.How will the pole be supported and how high?

R T Majuta
DSD City of Tucson
2/10/09
02/17/2009 DAVID RIVERA ZONING REVIEW Denied David Rivera
Zoning Review Section
February 17, 2009

It is not clear what additional process is required due to the redefining of the NUOS area over lot 1. Contact Patricia Gehlen for more info on what will have to be processed prior to final approval of the site plan and building plans.

See the comments by the Landscape Reviewer and the DUPD reviewer related to the SCZ and NUOS areas.

These issues must be addressed before the plans can be approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2009 CPIERCE1 OUT TO CUSTOMER Completed
06/24/2009 SUE REEVES REJECT SHELF Completed