Permit Number: T08CM03457
Parcel: 117041900

Address:
127 W 5TH ST

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM03457
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2008 DAVE MANN FIRE REVIEW Approved
11/07/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. 1/8" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL FOR 3/32" LETTERING IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY THE DRAWINGS SUBMITTED FOR CHECKING.
2. PROVIDE TWO SETS OF CALCULATIONS.
3. SHEET S1.1; FOUNDATION PLAN: NOTE INDICATES TOP OF FOOTING IS 96'-0", WHILE SECTIONS 1 AND 2 INDICATE TOP OF FOOTING IS 5' BELOW SLAB (95'-0"?). CLARIFY.
4. SHEET S1.2; TOWER ROOF FRAMING PLAN: SHOW CONNECTION OF 3/8" SAG RODS TO FRAMING MEMBERS.
5. SHEET S1.3; DOCK ROOF FRAMING PLAN: NOTE SIZE OF STRUCTURAL MEMBER (HSS 6X6X0.125) ON NORTH/SOUTH PORTION OF ROOF.
6. SHEET S2.0; GENERAL: INCLUDE CONNECTIONS (WELDS/BOLTS/SCREWS/ETC.) FOR ALL MEMBERS SHOWN IN SECTIONS.
11/12/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/14/2008 JASON GREEN ENGINEERING REVIEW Approved DATE: November 14, 2008
SUBJECT: Clock Tower Entrance and Loading Dock Canopies to an Existing Warehouse- Engineering Review
ADDRESS: 127 W 5th Street, Tucson Arizona 85705
REVIEWER: Jason Green, CFM
ACTIVITY NUMBER: T08CM03457


SUMMARY: The Floodplain Use Permit and site plan were received and reviewed by Engineering Division. The Floodplain Use Permit application (T08OT02525) and site plan (T08CM03457) will be issued for construction of a clock tower entrance and loading dock canopy additions to an existing warehouse located within the FMEA SFHA Zone AE. Engineering Division recommends approval of the Floodplain Use Permit and site plan.


CONDITIONS OF PERMIT:

The associated improvements are with permit activity number T08OT02525 (Floodplain Use Permit) and T08CM03457 (site plan).

The applicant attests to the fact that the plans and documents submitted represent all of the improvements that will be constructed and are included in the construction plans and/or documents herewith.

This permit is specific to the construction of a clock tower entrance and loading dock canopy additions as shown on this site plan and structural calculations sheets. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.

Copies of the site plan/permit documents shall be kept in a readily accessible location on site at all times.

If you have any questions, I can be reached at (520) 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
12/22/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
12/22/2008 SUE REEVES REJECT SHELF Completed