Permit Number: T08CM03436
Parcel: 13502134H

Address:
7090 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03436
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2009 GERRY KOZIOL WWM REVIEW Approved
04/16/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The condensate drains have not been sized per the requirements of Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. Show how the exposed PVC condensate drainage pipe is to be protected from the sunlight. Reference: Section 2.33, IAPMO IS 9-2003 (UPC 2006)
04/17/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
2. Revise Plumbing Note #14. A Proset trap guard is not approved for use as a trap protector. Reference: Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2009 GERARDO BONILLA OUT TO CUSTOMER Completed
05/06/2009 SUE REEVES REJECT SHELF Completed