Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM03436
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/10/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
02/10/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/19/2009 | GERRY KOZIOL | WWM | REVIEW | Denied | ISSUED WITH GREASE INTERCEPTOR NEED PCRWRD/3RD FLOOR/IRD REVIEW & APPROVAL OF LOCATION/METHOD OF CONNECTION TO EXSISTING ON-SITE PRIVATE SEWER (EASEMENTS, JOINT USE AGREEMENTS, CAPACITY, ETC) 740-6544 |
02/25/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/25/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the sanitary waste, grease waste, and storm drainage designs as shown on sheets P1.2, P3.1, and P3.3. There is no storm sewer located on the project site (see sheet UT01) and the grease waste for the building has apparently been replaced by the "storm sewer". In addition, since the roof drains and leaders do not terminate over an area that can absorb the condensate waste without surface drainage (see sheet SD1), the condensate drains cannot terminate over the roof drains. Reference Section 103.2.3, UPC 2006 and Section 307.2.1, IMC 2006, as amended by the City of Tucson. (Note: the tables referenced in the roof drain calculations on sheet P3.4 are from the IPC and not from the UPC; also, Table 1106.7 is not included in the IPC.) 2. The civil drawings (SP1 and SD1) show a reduced pressure backflow prevention assembly located in a location accessible to Tucson Water personnel. Is the reduced pressure backflow prevention assembly shown on sheets P1.0 and P3.0 supposed to be in addition to the one shown on the civil drawings? If it is, include its pressure drop in the water pressure calculations. (Reduced pressure backflow prevention assemblies for the building water service are required to be installed in locations accessible to Tucson Water. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf) |
02/26/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the size of the condensate drain for rooftop unit P-1. Revise the termination of the condensate drains to comply with the requirements of Section 307.2.1, IMC 2006, as amended by the City of Tucson. |
03/06/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/13/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
04/13/2009 | SUE REEVES | REJECT SHELF | Completed |