Review Details: REVISION - - 1ST
Permit Number - T08CM03216
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | (These comments are for revision delta-3 only) 1. Coordinate the sizes for the water supplies to sink P3A (in room 209) as shown on sheets P1 and P2. 2. Correct the size of the cleanout for P5 in room 205 (2" WCO for a 3" waste). Reference: section 708.7, IPC 2006. 3. Provide a cleanout for the 4" drain serving P1 and P2 in room 204 (2" WCO shown). Reference: section 708.7, IPC 2006. |