Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/12/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | (These comments are for revision delta-3 only) 1. Coordinate the sizes for the water supplies to sink P3A (in room 209) as shown on sheets P1 and P2. 2. Correct the size of the cleanout for P5 in room 205 (2" WCO for a 3" waste). Reference: section 708.7, IPC 2006. 3. Provide a cleanout for the 4" drain serving P1 and P2 in room 204 (2" WCO shown). Reference: section 708.7, IPC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/18/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |