Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM02918
Parcel: 13413057W

Address:
51 S PANTANO RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM02918
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2008 DAVE MANN FIRE REVIEW Approved
09/12/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. ONLY ONE SET OF CALCULATIONS WAS PROVIDED FOR THE 30' X 30' SHADE STRUCTURE. TWO IS REQUIRED. THERE WAS A SET OF CALCULATIONS FOR THE 40' X 50' STRUCTURE INCLUDED.
2. PAGE 3000: SOIL PARAMETERS INDICATE USING 2006 IBC TABLE 1804.2 FOR PRESCRIPTIVE FOUNDATION PRESSURES, BUT ALSO INDICATE A GEOTECHNICAL REPORT. THIS REPORT WAS NOT SUBMITTED. CLARIFY METHOD BEING USED TO DETERMINE ALLOWABLE SOIL PRESSURE.
3. PAGE 3000: DETERMINE IF THE FOOTING TYPE 03 OR 04 IS TO BE USED ON THIS PROJECT, AND OMIT THE UNUSED SECTION. IF BOTH OPTIONS ARE TO BE USED, INDICATE ON A PLAN THE FOOTING TYPE AND ITS LOCATION.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2008 CPIERCE1 OUT TO CUSTOMER Completed
09/22/2008 SUE REEVES REJECT SHELF Completed