Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM02888
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. HOW DO WE EPOXY VERTICAL WALL REINFORCING INTO THE EXISTING FOOTING? VERIFY.
2. SHEET S-1; SECTION 2: VERTICAL REINFORCING CALLED OUT IN SECTION (#5 @ 48" OC BETWEEN EXISTING WALL REINFORCING) NEEDS TO RELATE TO CALCULATIONS (#5 @ 32" OC). WHAT IS EXISTING VERTICAL REINFORCING SIZE AND SPACING?
3. REVIEW ADDITION OF NEW FOOTING TO EXISTING FOOTING. DOES THIS MATCH CALCULATIONS?
08/26/2008 JASON GREEN ENGINEERING REVIEW Approved
09/04/2008 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
09/04/2008 DROBEY1 FIRE REVIEW Needs Review
09/04/2008 DROBEY1 ZONING REVIEW Needs Review