Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T08CM02888
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/26/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. HOW DO WE EPOXY VERTICAL WALL REINFORCING INTO THE EXISTING FOOTING? VERIFY. 2. SHEET S-1; SECTION 2: VERTICAL REINFORCING CALLED OUT IN SECTION (#5 @ 48" OC BETWEEN EXISTING WALL REINFORCING) NEEDS TO RELATE TO CALCULATIONS (#5 @ 32" OC). WHAT IS EXISTING VERTICAL REINFORCING SIZE AND SPACING? 3. REVIEW ADDITION OF NEW FOOTING TO EXISTING FOOTING. DOES THIS MATCH CALCULATIONS? |
| 08/26/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/04/2008 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/04/2008 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 09/04/2008 | DROBEY1 | ZONING | REVIEW | Needs Review |