Permit: T08CM02888
Permit Details
Apply Date:
08/26/2008
Applicant:
N/A
Description:
ADDITION:BACK UP GENERATOR & PAD
Contractors:
- TRUSSNET U S A DEVELOPMENT CO INC
Permit Reviews
Permit Number - T08CM02888
Permit Status: Expired
Permit Description: ADDITION:BACK UP GENERATOR & PAD
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/26/2008 | COMMERCIAL-BLDG/FIRE/ZONING/ENG | 09/04/2008 | COMPLETED |
| 09/04/2008 | COMMERCIAL-BLDG/FIRE/ZONING/ENG | 09/04/2008 | COMPLETED |
| 09/04/2008 | COMMERCIAL-BLDG/FIRE/ZONING/ENG | 09/04/2008 | COMPLETED |
| 09/04/2008 | COMMERCIAL-BLDG/FIRE/ZONING/ENG | 09/04/2008 | COMPLETED |
| 09/04/2008 | PLANS OK TO SUBMIT - SITE | 09/04/2008 | COMPLETED |
| 09/04/2008 | SITE | 10/10/2008 | COMPLETED |
| 09/04/2008 | OTHER | 10/10/2008 | COMPLETED |
| 10/10/2008 | RESUBMITTAL - SITE | 11/07/2008 | ACTIVE |
| 10/10/2008 | OTHER | 10/30/2008 | ACTIVE |
Outstanding Activity Conditions
Permit Number - T08CM02888
Permit Status: Expired
Permit Description: ADDITION:BACK UP GENERATOR & PAD
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/26/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08CM02888
Permite Description: ADDITION:BACK UP GENERATOR & PAD
Total Outstanding Inspections - 8
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - PROGRESS | N/A | Not Inspected | ||
| MECHANICAL - FINAL | N/A | Not Inspected | ||
| ZONING - FINAL | N/A | Not Inspected | ||
| 01/06/2009 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ONLY SERVICE CONDUCTORS IN SERVICE DISCONNECT 2. CANNOT STACK LUGS 3. NEED SIGNAGE PER 703.8 4. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL 5. NEED SUPPLEMENTARY GROUNDING ELECTRODE 6. SECURE RECEPTACLE BOX INSIDE OF GENERATOR ENCLOSURE 7. UNCOVER CONDUITS AT GENERATOR TO INSPECT 8. SUPPORT CONDUITS UNDER TRANSFER SWITCH 9. VERIFY GROUND RING AT GENERATOR PAD 10. TRANSFER SWITCH DOES NOT APPEAR TO BE AS PER PLANS -- NO FUSES OR SERIES LIGHTING 11. INSTALL CIRCUITS AS PER PLANS |
| 01/09/2009 | ELECTRIC - UFER | N/A | Partial Approval | IVRS - Inspection :* 1. OK GROUNDING ELECTRODE SYSTEM 2. OK UNDERGROUND 3. COMPLETE ITEMS #3,8,10 FROM INSPECTION ON 1/6/09 |
| 01/09/2009 | ELECTRIC - UNDERGROUND | N/A | Partial Approval | IVRS - Inspection :* |
| 01/09/2009 | ELECTRIC - INTERMEDIATE | N/A | Partial Approval | IVRS - Inspection :* |
| 01/13/2009 | BUILDING - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* PERMIT NEEDS TO BE ON SITE |
Completed Inspections
Permit Status: Expired
Permit Number: T08CM02888
Permit Description: ADDITION:BACK UP GENERATOR & PAD
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2008 | EXCAVATION/LAYOUT REBAR & ZON | MHENSON | Approved | IVRS - Inspection :* GENERATOR PAD AND WALL FOOTING STEEL OK TO BE SPECIAL INSPECTED |
| 12/30/2008 | STEM WALL/RETAINING WALL | MHENSON | Approved | IVRS - Inspection :* 1) NEEDS ELECTRIC ADDED TO PERMIT DONE BY LERAY |
| 01/13/2009 | REINFORCED MASONRY PRE-GROUT | MHENSON | Approved | IVRS - Inspection :* |