Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM02835
Parcel: 120086070

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM02835
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2008 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T08CM02835

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets (clouded revision notation is not necessary for comment changes).

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

SITE PLAN:

1. Indicate the location of buildings, utility meters and gas & water lines from property line to building, R106.1.1.

FLOOR PLANS:

1. Show compliance with R310 providing egress from bedrooms by providing a minimum net clear opening dimension of 24" height and 20" width.

SECTIONS - DETAILS:

1. Provide a interior wall detail clearly illustrate materials, sizes and connections, R106.1.1.
2. Note or detail interior wall covering (1/2" GWB), R702.3.
3. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.
4. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.

PLUMBING PLANS:

1. Provide a plumbing design using a single code, 2006 UPC or 2006 IRC.
2. Note and specify all piping materials, UPC 301.1.1. IRC P2608. Include existing building sewer pipe material and new water pipe size, UPC 718.3.
3. Provide protection of (indoor rated) equipment located outdoors, UPC 508.27. IRC G2406.3.
4. Provide water hammer arresters wherever quick-closing valves are installed in a water distribution system. The devices should conform to ASSE 1010-2004. Water hammer arresters are required for clothes washers, dishwashers and refrigerator water connections, UPC 609.10. IRC P2903.5.

MECHANICAL PLANS:

1. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1. Show R-4.2 insulation when ducts are located in an unconditioned space (chase) inside the thermal envelope, IECC 503.2.7 (City of Tucson Amended).
2. Show the kitchen exhaust fan minimum 100 CFM rating, M1507.3.

ELECTRICAL PLANS:

1. Smoke alarms are required outside (Kitchen) each separate sleeping area, R313.2.
2. Show a GFCI receptacle outlet on the same level within 25' of exterior HVAC equipment, E3801.11.
3. Note that combination type arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.12.

OUTDOOR LIGHTING CODE

1. The product sheet provided shows an unshielded fixture (Fixture "A"). Full cut-off fixtures have no emittance above the nadir (fixtures are completely opaque above and to the lowest point of the lamp). Fixtures may be exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2. Show fixture 'A' as unshielded on the Fixture Schedule.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2008 SUE REEVES REJECT SHELF Completed
09/24/2008 CINDY AGUILAR OUT TO CUSTOMER Completed