Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T08CM02588
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/31/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/31/2008 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/31/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/31/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM02588 7/31/08 1. Minimum font size is 1/8". Panel schedules, line diagrams, fault calculations, and load summaries not reviewed. 2. Contractor has stated that scope of work entails the addition of pump and lighting for fountain, powered from existing panel. Plans shall clarify which equipment is new as opposed to which is existing. Fault calculations should not be necessary if service and all panels are existing. 3. Specify conduit and conductor size and type for all new runs. 4. Provide disconnecting means for pump. NEC 430. 5. Demonstrate compliance with Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 6. Resubmitted design shall demonstrate compliance with NEC 680. |
| 08/04/2008 | CAGUILA1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/04/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |