Permit Number: T08CM02588
Parcel: 13320129D

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM02588
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/31/2008 TERRY STEVENS ZONING REVIEW Approved
07/31/2008 JASON GREEN ENGINEERING REVIEW Approved
07/31/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM02588 7/31/08

1. Minimum font size is 1/8". Panel schedules, line diagrams, fault calculations, and load summaries not reviewed.
2. Contractor has stated that scope of work entails the addition of pump and lighting for fountain, powered from existing panel. Plans shall clarify which equipment is new as opposed to which is existing. Fault calculations should not be necessary if service and all panels are existing.
3. Specify conduit and conductor size and type for all new runs.
4. Provide disconnecting means for pump. NEC 430.
5. Demonstrate compliance with Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
6. Resubmitted design shall demonstrate compliance with NEC 680.
08/04/2008 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2008 CINDY AGUILAR OUT TO CUSTOMER Completed