Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T08CM02312
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/31/2008 | HENRY DURAZO | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS T08CM002312 " SITE PLAN: " FOUNDATION " FLOOR " STRUCTURAL " ELEVATION " DETAIL " PLUMBING " MECHANICAL " ELECTRICAL " OLC " IECC Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets (clouded revision notation is not necessary for comment changes). The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html GENERAL NOTES: " All code references to the International Residential Code shall be changed from 2003 to 2006 with appropriate paragraph references. SITE PLAN: 1. Indicate the location of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. 2. Show the water pipe size between the meter to the building and point of connection for new plumbing. Show the point of connection for the proposed hot and cold branches. The supply pipe must be sized for the calculated load, 2006 UPC 610.1. 3. Specify overhead or underground electrical service. Overhead service for a new dwelling requires an appeal to the Building Official, UAC amendment section 108. FOUNDATION PLANS: 1. Locate and detail all footings (R301.1) for the following: " Interior bearing walls " Posts or columns 2. All slabs (i.e. patio slabs and pads outside of doors) shall be shown and their thickness specified. Indicate the slopes for exterior slabs. 3. Indicate the slopes for garage slabs, R309.3. 4. Provide a landing or floor surface at all exterior doors. A landing must be at least as wide as the door it serves and 36" in the direction of travel, R311.4.3. 5. Show or note an 8" minimum separation of untreated exterior framing above finished grade, R319.1 item 2. 6. Show or note a 6" minimum separation of untreated exterior posts or columns above finished grade and support by metal pedestal with 1" space above the floor, R319.1.4 exception 1. 7. Show compliance with termite treatment, R320 as amended. 8. Revise the foundation requirements for accommodating all loads, R401.2. 9. Note that grade away from foundations shall fall min 6" within the first 10', R401.3. 10. Show all foundation hold-downs for alternate brace wall panels on the Foundation Plan, R403.1.6. Required for continuously sheathed wall sections less than 4' (with 8' height) adjacent to opening over 85% of wall height, R602.10.5. 11. Revise the Alternate Braced Wall Panel notation showing a device and an installation method that provides the required 1800 LBS uplift capacity, R602.10.6. The PAHD42 is rated less than required 1800 LBS when installed with end distance less than 8". The HPAHD22 is rated less than 1800 LBS when installed with end distance less than 8" and with fewer than 23 -16d nails. FLOOR PLANS: 1. Show entire floor plan labeling all rooms and spaces, R106.1.1. Include dimensions and show all doors, windows, fixtures and appliances in the construction area. 2. Show that each water closet is located in a clear space not less than 30" wide (centered 15" from finished wall or fixture) and has a clear space in front not less than 24", R307.1 & UPC 407.6. 3. Provide all window sizes and types, and designate the operable portion of windows, as well as the location of tempered glass (within 18" of the floor, 24" of doorways, and when less than 60" above tub/shower floors), R308.4. 4. Show the location of tempered glass adjacent to stairways and landings within 36" of a walking surface and when less than 60" above the surface, R308.4.10. 5. Show a ½" gypsum board (garage side) on all walls common to the garage and house or other fire rated product in compliance with R309.2. 6. Show the garage floor direction of slope, R309.3. STRUCTURAL PLANS: 1. Specify design criteria on plans. Provide values for floor dead load and live load as well as roof dead load and live load, R301.1. (City of Tucson Amended). 2. Provide complete roof and floor framing plans. Show size, spacing and span of all framing members, trusses, joists, rafters, beams, glue-lams, lintels, headers, ledgers and blocking, R301.1. 3. Detail all brace wall connections from the foundation to the roof sheathing, R602.10.8. 4. Provide a complete braced panel layout showing panels at the ends (within 12.5') of all wall lines and additional panels centered at least every 25' O.C., Table R602.10.1. Show all exterior wall bracing and interior wall line bracing at intervals not exceeding 35' (50' exception) from exterior wall lines, R602.10.1.1. 5. Locate and identify brace wall panel materials (min 3/8" OSB) and locations along with the appropriate nailing schedule (8d @ 6" o/c edge & @12" o/c field), R602.10.6. 6. Continuous structural panel sheathing shall comply with Table R602.10.5 that is limited to 10' wall lengths, R602.10.5. Show interior wall line bracing at intervals not exceeding 35' (50' exception) from exterior wall lines, R602.10.1.1. 7. Show minimum 24" structural panels (Table R602.10.5) are corners (Figure R602.10.5) when providing continuous sheathing, or provide alternate braced wall panels, R602.10.6 at corner locations of less than 24" length with 1800 LB tie-down capacity (Table R602.10.6). 8. Brace wall panel requirements have not been met for the garage door opening with adjacent wall panels less than 32", R602.10.6. The single portal Alternate Braced Wall design requires sheathed panel nailing to header, 4,200 LBS uplift capacity tie-downs, and 1,000 LBS post straps top and bottom, Figure R602.10.6.2. 9. Specify the ICF evaluation report number and manufacturer, or show design compliance with all appropriate sections of R611 with details of connections and material sizes. 10. Provide joist sizes and spacing in compliance with Table R802.4. 11. Provide rafter sizes and spacing in compliance with Table R802.5.1. 12. Note or detail trimmers, headers and framing anchors (show sizes) at framed door and window openings, R802.9. ELEVATIONS: 1. Indicate all materials used; stucco, concrete block, glass block, roofing system, siding, veneer, etc, R301.1. 2. Note and specify all roof slopes appropriate with selected material, R901.1. (Minimum allowable slope for Built-up roof is ¼" per foot, R905.9.1. Minimum allowable slope for Roll roofing is 1" per foot, R905.5.2.) SECTIONS - DETAILS: 1. Provide a building cross-section. More than one may be required to clearly illustrate materials, sizes and connections, R106.1.1. 2. All cross-sections shall be cross-referenced to the respective floor plan and framing plan, R106.1.1. 3. Show fiber-cement board or glass mat e d. gypsum backers for tiled walls in tub and shower areas, R702.4.2. WATER: 1. Hose bibs require backflow preventers, UPC 603.2.3. IRC P2902.4.3. 2. Provide minimum 40 PSI - maximum 80 PSI water pressure, IRC P2903.3. 3. Each dwelling unit requires an individual accessible water supply shut off, UPC 605.3. IRC P2903.9.1. 4. Each dwelling unit of the duplex requires an individual water meter, IPC 301.4.1 WASTE AND VENTING: 1. Show a clean out at the kitchen sink area UPC 707.4 W/ State amendment. TOP ELECTRICAL PLANS: 1. Note on plan that all electrical work shall comply with 2006 IRC chapters 33 - 42. 2. Provide a minimum service conductor of 100 AMP for each dwelling and conductors with minimum rating of #4 copper 75 degree C, E3502.1 & E3503.1. 3. Provide a feeder load calculation for the new sub-panel. The 40% demand factor may not be applied for feeder loads, E3604.2. 4. Note that light fixtures in clothes closets shall be installed in accordance with E3903.11. 5. Submit information on under floor heater for approval . OUTDOOR LIGHTING CODE 1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. 2. Provide cut sheets for all full cut-off fixtures showing the lamp placement and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). Fixtures may be exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2. 3. Include all exterior fixtures on the property in the outdoor lighting calculations (OLC 3.1.2). 4. The product sheet provided shows an unshielded fixture (Fixture "A"). Full cut-off fixtures have no emittance above the nadir (fixtures are completely opaque above and to the lowest point of the lamp). Fixtures may be exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2. The existing Fixtures "B" appear to have exceeded the unshielded lumen limit; therefore the new fixture must be of the full cut-off FCO style. Select an appropriate fixture and label the new fixture as Full Cut-Off on the Electrical Plan. 5. Show compliance with City of Tucson Outdoor Lighting Code; the total property lighting limit for area E3 is 55,000 lumens per acre and the unshielded limit for area E3 is 12,000 lumens per acre. Include all exterior fixtures on the property in the calculations. Separately show the fixture wattage both full cut-off and unshielded styles for determining exterior lighting limits. Review guidance: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf If you have any questions please contact: Enrique Durazo (520) 954 0152 City of Tucson Residential Plan Re |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/04/2008 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 08/04/2008 | SUE REEVES | REJECT SHELF | Completed |