Permit Number: T08CM02038
Parcel: 13819032B

Review Status: Completed

Review Details: SITE

Permit Number - T08CM02038
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2008 SREEVES1 ADA REVIEW Passed
10/21/2008 MARTIN BROWN FIRE REVIEW Approved
10/21/2008 RONALD BROWN ZONING HC SITE REVIEW Denied 21 OCTOBER 2008
T08CM02038/TUCSON COMMUNITY CHURCH SOUTHWEST
SITE ACCESSIBILITY REVIEW
REVIEWED BY RON BROWN

SITE ACCESSIBLE REVIEW
2006 IBC/ICC 117.1

DENIED: SEE COMMENTS BELOW

I. SHEET 1 of 19:
A. PLEASE PROVIDE PREVIOUSLY APPROVED SITE PLAN.
B. SHOW ACCESSIBLE ROUTE CONNECTION TO PUBLIC RIGHT OF WAY PEDESTRIAN WAY
C. IDENTIFY ACCESSIBLE ROUTE AND PROVIDE SPOT GRADE ELEVATIONS SHOWING COMPLIANCE WITH ICC/ANSI 117.1, SECTION 403.3
D. FOR SITE PLAN, DETAILS "A" AND "F":
1. PROVIDE AND REFERENCE TO A SIGN ELEVATION DETAIL.
2. PROVIDE A SURFACE MOUNTED CURB DETAIL FOR ACCESSIBLE ROUTE SEPARATION FROM THE VEHICLE PAVING EXCEPT AT ACCESS AISLES. REFERENCE ZONING COMMENTS FOR EXACT SEPARATION REQUIREMENTS.
E. ACCESSIBLE ROUTE IN FRONT OF ALL ACCESSIBLE PARKING WILL NEED TO BE CONCRETE AS PER ZONING DEVELOPMENT STANDARDS. REFERENCE ZONING COMMENTS.
F. IDENTIFY SLOPE AT ACCESSIBLE PARKING TO BE A MAXIMUM OF 2% SLOPE BOTH WAYS.
G. PROVIDE DETECTABLE WARNINGS AT BOTH ENDS OF MARKED CROSSING AS PER ICC/ANSI 117.1, SECTIONS 40406.12 AND 406.14.

END OF REVIEW
10/29/2008 ANDREW CONNOR NPPO REVIEW Passed
10/29/2008 ANDREW CONNOR LANDSCAPE REVIEW Passed
11/06/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines and fire hydrants
c. the location of the gas meter (if present)
d. the location and size of the public sanitary sewer
e. the location, invert, and rim elevation of the next upstream and downstream manholes and cleanouts
f. the first floor elevation
Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006.
11/07/2008 PAUL MACHADO ENGINEERING REVIEW Denied To: Ric Espiriti DATE: November 7, 2008
Tucson Community Church
2610 E. Broadway Blvd., Ste. E
Tucson, Arizona, 85716

SUBJECT: Tucson Community Church, 265 W. Valencia Rd.
Floodplain use permit T08OT02471 (First Review)
T15S, R13E, Section 13

RESUBMITTAL REQUIRED: Floodplain use permit and Site Plan

The Floodplain Use Permit (FUP) and Site plan (SP) cannot be approved at this time. Please address the following review comments prior to the next submittal.

Flood plain use permit and Site Plan:

1. An appraisal of the existing structure by a licensed professional appraiser is required for the approval of the FUP. The appraisal shall not include the value of land and shall only be for the value of the existing structure alone.
2. The Site plan and Building permit cannot be approved prior to the approval of the Floodplain Use Permit. Re-submit the FUP, SP and bldg. plan with the appraisal.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/265 W. Valencia Rd._FUP denial letter

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2008 CPIERCE1 OUT TO CUSTOMER Completed
11/18/2008 SUE REEVES REJECT SHELF Completed