Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM02038
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/20/2008 | SREEVES1 | ADA | REVIEW | Passed | |
10/21/2008 | MARTIN BROWN | FIRE | REVIEW | Denied | Please provide code review analysis, including occupant load information. |
10/21/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. STRUCTURAL CALCULATIONS; SHEET #1: LATERAL LOAD FOR SEISMIC MUST BE CALCULATED AND COMPARED TO WIND LOADS. 2. STRUCTURAL CALCULATIONS; SHEET #1: LATERAL LOAD FOR WIND MUST BE CALCULATED, BUT SINCE THIS IS INTERIOR IMPROVEMENT, SEISMIC ANALYSIS WILL CONTROL. REFERENCED TABLE 1609.6.2.1 IS FROM THE 2003 IBC AND CAN NOT BE USED. 3. SHOW THE LATERAL CALCULATIONS AND APPLY THOSE LOADS TO THE RESISTING ELEMENTS OF THE NEW CONSTRUCTION. PROVIDE CONNECTIONS AND DETAILS PERTINENT TO THE LATERAL ANALYSIS. 4. SHEET S-1; CALCULATIONS SHEET #7: CALCULATIONS INDICATE FLOOR JOISTS SHOULD BE SPACED AT 16" O.C. WHERE SUPPORTING A WALL ABOVE. DRAWINGS DO NOT INDICATE THAT. CLARIFY. 5. SHEET S-1; CALCULATIONS SHEET #10: NOTE ON THE FRAMING PLAN AT THE CONTROL ROOM THAT THE 4X12 BEAM REQUIRES A STEEL PLATE AND BOLTS. 6. SHEET S-3; SECTIONS 3 AND 4: THE TOP OF THE INTERIOR PARTITIONS MUST BE BRACED TO THE ROOF STRUCTURE TO RESIST HORIZONTAL LOADS REQUIRED BY SECTION 1607.13 OF THE 2006 IBC. PROVIDE DETAILS AND CONNECTIONS (CAN NOT USE CEILING GRID SYSTEM FOR LATERAL SUPPORT). 7. PROVIDE CONTRACTOR'S WRITTEN COST ESTIMATE FOR THIS PROJECT. |
10/22/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
10/30/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
11/04/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project; 265 W Valencia Rd. T I T08CM02038 This project has been denied for the following; 1.Sheet E-1 on the 2nd floor, the power circuit for the receptacles in the storage area has not been assigned a circuit number. 2. Sheet E-2 , circuit B-3 has been assigned to two circuits,2nd floor lighting and class room 2. 3. Sheet E-2, does not show emergency lighting in Sanctuary area . 4.Sheet E-3 circuits 1 and 3 in panel E (lights not located). Ray T Majuta DSD City of Tucson ELect Plan Ck 11/12/08 |
11/05/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the note on the second floor plumbing plan, "3/4" W to below". Reference: Section 103.2.3, UPC 2006. 2. Clarify the nature of the piping associated with the air compressor that is being removed on the second floor plumbing plan. Reference: Section 103.2.3, UPC 2006. 3. Provide a site drawing showing the size, route, and slope of the building sewer. Reference: Section 103.2.3, UPC 2006. |
11/05/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/06/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006. |
11/06/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the balancing data for each of the existing air conditioning systems and the existing exhaust fans, including supply CFM, exhaust CFM, and outside air CFM. Reference: Sections 106.3.1, IMC 2006. 2. Correct the arithmetic errors in the ventilation calculations. |
11/07/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Ric Espiriti DATE: November 7, 2008 Tucson Community Church 2610 E. Broadway Blvd., Ste. E Tucson, Arizona, 85716 SUBJECT: Tucson Community Church, 265 W. Valencia Rd. Floodplain use permit T08OT02471 (First Review) T15S, R13E, Section 13 RESUBMITTAL REQUIRED: Floodplain use permit and Site Plan The Floodplain Use Permit (FUP) and Site plan (SP) cannot be approved at this time. Please address the following review comments prior to the next submittal. Flood plain use permit and Site Plan: 1. An appraisal of the existing structure by a licensed professional appraiser is required for the approval of the FUP. The appraisal shall not include the value of land and shall only be for the value of the existing structure alone. 2. The Site plan and Building permit cannot be approved prior to the approval of the Floodplain Use Permit. Re-submit the FUP, SP and bldg. plan with the appraisal. If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4932 office (520) 879-8010 fax C:/265 W. Valencia Rd._FUP denial letter |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/18/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
11/18/2008 | SUE REEVES | REJECT SHELF | Completed |