Permit Number: T08CM01986
Parcel: 12009317A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01986
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2008 TERRY STEVENS ZONING REVIEW Denied 09/19/2008

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
09/22/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. 2 SETS OF DRAWINGS REQUIRED FOR APPROVAL.
2. REFERENCE PREVIOUS COMMENT 3 ON SHEET A4.0: TITLE UNDER THE PLAN STILL INDICATES 'PRELIMINARY'. CLARIFY.
3. 2 SETS OF PREFABRICATED METAL BUILDING DRAWINGS REQUIRED.
4. REFERENCE PREVIOUS COMMENT 7 ON SHEET A2.0: STRUCTURAL SECTIONS 107 AND 108 ON SHEET S2.0 STILL ARE NOT COORDINATED WITH ARCHITECTURAL SECTIONS 1 AND 2 ON SHEET A2.0 (1/2" BLOCKOUT AND NO CMU WALL INDICATED). CLARIFY.
5. SHEET S1.0; FOUNDATION PLAN: COLUMN FOOTING F1 AT GRIDS 4 AND G SHOULD BE AT GRIDS 8 AND E. REVISE.
6. SHEET S1.0; FOUNDATION PLAN: F2 FOOTING AT GRIDS 2 AND G IS LARGER THAN 2'-0" SQUARE AS INDICATED IN FOOTING SCHEDULE, SINCE 2'-0" DIMENSION FROM GRID 1 TO 2. CLARIFY.
09/22/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
09/23/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the envelope energy calculations to reflect the building shown on the plans.
2. Clarify the manner in which the fan coils are being supported on the ceiling joists.
3. Correct the common area ventilation calculations.
4. The minimum insulation for ducts located in indirectly conditioned spaces within the building envelope is R-4.2 (installed). Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson
09/23/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide backflow protection for the water connection to the steam generator.
2. Correct detail 204 to reflect the manner in which the water heater is to be supported on the ceiling joists.
3. Correct the labeling on detail 212.
09/23/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/24/2008 CPIERCE1 WWM REVIEW Needs Review