Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/16/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM01582 5/16/08

1. Show panel and circuit number for all lights.
2. Show location of electrical panel on plans.
3. Provide panel schedule and load calculations.
4. Indicate total count of T8 flourescent bulbs.
5. Provide disconnecting means. NEC 600.6.
6. Demonstrate compliance with the Tucson Lighting code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
05/16/2008 MARTIN BROWN FIRE REVIEW Approved
06/10/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/10/2008 DROBEY1 ENGINEERING REVIEW Needs Review
06/10/2008 DROBEY1 ZONING REVIEW Needs Review