Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01423
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/02/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 05/02/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 05/02/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The indirect waste from the new bar sink shall not exceed 5 feet from the fixture outlet to the indirect waste receptor. Reference: section 801.3, UPC 2006. |
| 05/02/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 05/02/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/02/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/02/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/07/2008 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 05/07/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/07/2008 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 05/07/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 05/07/2008 | DELMA ROBEY | REJECT SHELF | Completed |