Permit Number: T08CM01385
Parcel: 137055310

Review Status: Completed

Review Details: SITE

Permit Number - T08CM01385
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2009 RBROWN1 ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
03/25/2009 MARTIN BROWN FIRE REVIEW Denied Please indicate location of existing and/or proposed fire hydrants, with dimensions to property lines. Refer to C.O.T. amendments to 2006 IFC Section 503 for spacing requirements.
03/25/2009 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T08CM01385
5315 S. Call Santa Cruz
Site Plan

TRANSMITTAL DATE: 03/31/09

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The parking calculations provided based on 1 space per 100 sq. ft of GFA is incorrect. The parking calculations for this site is based on shopping center criteria. 1 space per 200 sq. ft. of GFA is the correct ratio. Revise calculations on sheet C-1.

2. Provide wheel stop curbs at the front of the handicap parking spaces along the west side of the proposed building. Required because of the pedestrian circulation path being flush with the asphalt. Provide location on detail A-C4 and on the site plan. Clearly indicate the minimum 2'-6" distance from the front of the parking space.

3. These comments are minor in nature and can be reviewed over the counter by setting an appointment with me.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T08CM01385doc
03/26/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. The governing accessible code is 2006 IBC, Chapter 11 and ICC/ANSI 117.1 2003 Edition. Change all detail references and accessible designs to meet these standards. Change all ADA references to ICC/ANSI 117.1. Please note governing code on cover sheet.
2. Please provide a detailed and dimensioned Architectural Site Plan.
3. The Connection to the building complex Accessible Route pedestrian way:
a. The fartest North island ramp with a detectable warning strip has a conflict with a site storm drainage concrete swale and the acessible route pathway. Please correct
b. The most Southerly ramp and dectable warning strip is not compliant with ICC/ANSI 117.1, Section 406.11.
c. The designed access to the building complex accessible route is rather complicated and lenghty. Please reference suggested alternative sketch show on plan.
4. All the Dectable Warnings provided in front of the accessible is not required by code.
5. Accessible Parking layout shown on C-3 is not as per detail on sheet C-4. Please coordinate.
6. The detectable warnings at the loading sidewalk ramps on the South side of the building are not required by code, Owner Option.
7. Provide concrete wheel stops for all accessible parking spaces.
8. Bottom of all main signs to be 7'-0" to finished grade.
9. All Detectable Warnings as required, need be only 2' deep.
04/07/2009 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. All lettering and dimensions shall be the equivalent of 12 point (0.12") or greater in size. Revise all undersized text on sheets LA.01 and LA.06 to meet this minimum standard.
DS 2-05.2.1.C

2. Per the approved landscape plan (sheet 7 of 27) for the Spectrum of Tucson, a minimum 30" continuous vegetative screen and 10-foot landscape border must be proveided along the east property line. In addition, a 6-foot masonry wall must be provided to screen dumpsters and the loading zone from the adjacent right-of-way. Indicate graphically and with labels all required screening on the landscape plan. LUC Table 3.7.2-I

3. Add the development plan case number (D06-009), the rezoning case number (C9-05-23), the WASH overlay zone case number (T06SA00069), and any other related case numbers to the lower right hand corner of all sheets of the site plan and landscape plan.
04/08/2009 PETER MCLAUGHLIN NPPO REVIEW Passed
04/10/2009 LOREN MAKUS ENGINEERING REVIEW Denied The site plan will be approved once the red lines from other reviewers are resolved.
04/20/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a copy of the last approved site plan for comparison.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2009 DELMA ROBEY OUT TO CUSTOMER Completed
04/28/2009 SUE REEVES REJECT SHELF Completed