Permit Number: T08CM01274
Parcel: 10602001C

Address:
3966 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM01274
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2008 DAVE MANN FIRE REVIEW Approved
04/30/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify intent of note in detail 8/A1.1, "water closet to be relocated." Provide plumbing plans if this is to be done. Reference: Section 103.2.3, UPC 2006.
2. A flow control device cannot be located under a floor sink and still be readily accessible. Reference: Sections 203.0 (accessible definition), 1014.1.1, and 1014.2.1, UPC 2006.
3. The wash and rinse compartments of a 3-compartment sink cannot be indirectly wasted. Reference: Sections 304.0 and 801.2.3, UPC 2006.
4. Provide a riser diagram for 3-compartment sink and floor sink installation. Reference: Section 103.2.3, UPC 2006.
05/01/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/19/2008 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2008 CPIERCE1 OUT TO CUSTOMER Completed
05/20/2008 SHANAE POWELL REJECT SHELF Completed