Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01274
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/24/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
04/30/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify intent of note in detail 8/A1.1, "water closet to be relocated." Provide plumbing plans if this is to be done. Reference: Section 103.2.3, UPC 2006. 2. A flow control device cannot be located under a floor sink and still be readily accessible. Reference: Sections 203.0 (accessible definition), 1014.1.1, and 1014.2.1, UPC 2006. 3. The wash and rinse compartments of a 3-compartment sink cannot be indirectly wasted. Reference: Sections 304.0 and 801.2.3, UPC 2006. 4. Provide a riser diagram for 3-compartment sink and floor sink installation. Reference: Section 103.2.3, UPC 2006. |
05/01/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/19/2008 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/20/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
05/20/2008 | SHANAE POWELL | REJECT SHELF | Completed |