Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM01274
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/22/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
04/22/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
04/22/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
04/22/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/22/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/22/2008 | DROBEY1 | WWM | REVIEW | Needs Review | |
04/22/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify intent of note in detail 8/A1.1, "water closet to be relocated." Provide plumbing plans if this is to be done. 2. A flow control device cannot be located under a floor sink and still be readily accessible. 3. The wash and rinse compartments of a 3-compartment sink cannot be indirectly wasted. 4. Provide riser diagram for 3-compartment sink and floor sink installation. |
04/22/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
04/22/2008 | DROBEY1 | FIRE | REVIEW | Needs Review | |
04/22/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/22/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |