Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM01161
Parcel: 133040030

Review Status: Completed

Review Details: OTHER

Permit Number - T08CM01161
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2008 JOSE ORTIZ DOT TRAFFIC REVIEW Denied June 13, 2008
ACTIVITY NUMBER: T08CM01161
PROJECT NAME: Desert Christian
PROJECT ADDRESS: 9415 E Wrightstown Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Site Plan (SP) or Traffic Impact Analysis (TIA); therefore a revised SP and TIA are required for re-submittal. The following items must be revised or added to the SP.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. The median opening for Desert Christian does not meet the Transportation Access Management spacing requirements. See Table 4-2 for a 35-mph roadway 450' is required between median openings. With the second median opening for the School this does not allow for safe stacking and transition for the driveway to the south. The median opening along the curve for the school is denied by Traffic Engineering. The Transportation Department supports one median opening along the Wrightstown curve for the existing driveway south of the School property.

3. Written justification for the sub standard median opening will need to be provided and approved for the proposed median layout.

4. The access points shall have 25' radius curb returns. (DS 3-01.0 figure 6)

5. A private improvement agreement (PIA) will be necessary for the proposed work to be performed within the Right-of-way. An approved site plan is required prior to applying for a PIA. Contact the PIA Coordinator for additional PIA information at 791-5550 ext. 1107.


If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov