Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM01058
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/19/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/19/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
08/20/2008 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
08/21/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
08/29/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The ventilation requirements shown in Table 403.3, IMC 2006 are independent from the State licensing requirements and from the occupancy rates in the IBC. Provide calculations based on Table 403.3 and Section 403.3.2, IMC 2006, as amended by the City of Tucson. |
08/29/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/29/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Amtrol Well-x-trol expansion tanks are not listed for use as thermal expansion tanks and are not sized the same way. Refer to the manufacturer's literature for thermal expansion tanks and provide the correct sizing calculations for the thermal expansion tank serving the two main water heaters (WH-1). Reference: Section 103.2.3, UPC 2006. 2. Comment not addressed. With the exception of general note #14 on sheet P-1 and the floor cleanouts, upper terminal cleanouts for many horizontal drainage pipes exceeding 5 feet in length are not evident on either the plumbing floor plan or the waste and vent schematic. Reference: Section 707.4, UPC 2006. |
09/11/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. THIS COMMENT WAS MADE ON THE FIRST AND SECOND REVIEWS. APPEAL TO THE BUILDING OFFICIAL WAS APPROVED FOR 3/32" FONT SIZE. SO PLEASE AT LEAST COMPLY WITH THIS FONT SIZE. FOR EXAMPLE, THERE IS A LOT OF 1/16" ON THIS JOB, INCLUDING QUITE SALIENT INFORMATION SUCH AS THE PANEL SCHEDULES. PLEASE PREVIEW YOUR PRINTOUTS BEFORE NEXT SUBMITTAL. 2. Re-assemble drawings such that they are all right-side-up please, that is, no upside down sheets. |
09/15/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
09/16/2008 | SREEVES1 | WWM | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/22/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
09/22/2008 | SUE REEVES | REJECT SHELF | Completed |