Permit Number: T08CM01058
Parcel: 13413057W

Address:
51 S PANTANO RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM01058
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/19/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
08/20/2008 PETER MCLAUGHLIN ZONING REVIEW Approved
08/21/2008 JASON GREEN ENGINEERING REVIEW Approved
08/29/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The ventilation requirements shown in Table 403.3, IMC 2006 are independent from the State licensing requirements and from the occupancy rates in the IBC. Provide calculations based on Table 403.3 and Section 403.3.2, IMC 2006, as amended by the City of Tucson.
08/29/2008 ROBERT SHERRY WATER REVIEW Approved
08/29/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Amtrol Well-x-trol expansion tanks are not listed for use as thermal expansion tanks and are not sized the same way. Refer to the manufacturer's literature for thermal expansion tanks and provide the correct sizing calculations for the thermal expansion tank serving the two main water heaters (WH-1). Reference: Section 103.2.3, UPC 2006.
2. Comment not addressed. With the exception of general note #14 on sheet P-1 and the floor cleanouts, upper terminal cleanouts for many horizontal drainage pipes exceeding 5 feet in length are not evident on either the plumbing floor plan or the waste and vent schematic. Reference: Section 707.4, UPC 2006.
09/11/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006. THIS COMMENT WAS MADE ON THE FIRST AND SECOND REVIEWS. APPEAL TO THE BUILDING OFFICIAL WAS APPROVED FOR 3/32" FONT SIZE. SO PLEASE AT LEAST COMPLY WITH THIS FONT SIZE. FOR EXAMPLE, THERE IS A LOT OF 1/16" ON THIS JOB, INCLUDING QUITE SALIENT INFORMATION SUCH AS THE PANEL SCHEDULES. PLEASE PREVIEW YOUR PRINTOUTS BEFORE NEXT SUBMITTAL.
2. Re-assemble drawings such that they are all right-side-up please, that is, no upside down sheets.
09/15/2008 GERRY KOZIOL WWM REVIEW Approved
09/16/2008 SREEVES1 WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2008 CPIERCE1 OUT TO CUSTOMER Completed
09/22/2008 SUE REEVES REJECT SHELF Completed