Permit Number: T08CM00838
Parcel: 13811073B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00838
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2008 HEATHER THRALL ZONING REVIEW Approved
03/14/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
03/14/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08CM00838 3/14/08

Please demonstrate that existing service entrance conductors are not overloaded. Currently of ampacity 750A. If they need to be up-sized that would effect fault calculations.
03/14/2008 ROBERT SHERRY WATER REVIEW Approved
03/14/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/14/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
03/14/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The trap and trap arm for a lavatory may not be increased more than one size larger than the minimum trap size shown in Table 7-3. Reference: Section 1003.3, UPC 2006.
2. Modify trap arm lengths to conform to Table 10-1, UPC 2006. Reference: Section 1002.2, UPC 2006.
3. The submitted water pressure calculations do not support the size of water piping to the water closet. Reference: Section 610.1, UPC 2006
03/14/2008 DAVE MANN FIRE REVIEW Approved
03/20/2008 CPIERCE1 WWM REVIEW Needs Review
03/20/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review