Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM00838
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 03/14/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006. 2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006. |
| 03/14/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08CM00838 3/14/08 Please demonstrate that existing service entrance conductors are not overloaded. Currently of ampacity 750A. If they need to be up-sized that would effect fault calculations. |
| 03/14/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/14/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/14/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 03/14/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The trap and trap arm for a lavatory may not be increased more than one size larger than the minimum trap size shown in Table 7-3. Reference: Section 1003.3, UPC 2006. 2. Modify trap arm lengths to conform to Table 10-1, UPC 2006. Reference: Section 1002.2, UPC 2006. 3. The submitted water pressure calculations do not support the size of water piping to the water closet. Reference: Section 610.1, UPC 2006 |
| 03/14/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/20/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 03/20/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |