Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM00726
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT CONCERNING 4" MASONRY WALL DESIGN AND DETAILING (COMMENT #4) AS DEPICTED IN SHEET A-2, SECTION 5, HAS NOT BEEN PROVIDED. NO CALCULATIONS FOUND. NO CONNECTIONS INDICATED AT TOP OR BOTTOM OF WALL TO RESIST LATERAL FORCES. 2. DID NOT LOCATE CALCULATIONS FOR NEW MECHANICAL UNIT ON EXISTING ROOF (MUST SHOW ADEQUACY OF EXISTING STRUCTURE FOR NEW LOAD). |
| 03/21/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/27/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/28/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/28/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. A permanently legible imprint of the registrant's seal and signature shall appear on either the cover, title, index page, or first sheet of each set of project specifications. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Show how the mechanical equipment (e.g. radiator, compression tank, etc.) is to be mounted. For example, a note in detail 6/M1 calls for the expansion tank to be "hung above the highest point in piping system on the roof." How is this to be done? Reference: Sections 303.1, 304.10, 305, and 306.5, IMC 2006. 3. Provide guards for equipment located within 10 feet of a roof edge that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.10, IMC 2006 |
| 04/01/2008 | SREEVES1 | ZONING | REVIEW | Passed | |
| 04/01/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/09/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 04/09/2008 | SUE REEVES | REJECT SHELF | Completed |