Permit Number: T08CM00587
Parcel: 122184340

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T08CM00587
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/29/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/29/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Power has been added for FCU-1 but it is shown on the 3rd floor, not the first floor.
2. Pumped condensate shall not be directly-connected to a lavatory tailpiece.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/31/2009 CPIERCE1 OUT TO CUSTOMER Completed