Permit Number: T08CM00587
Parcel: 122184340

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T08CM00587
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/15/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the access ladder shown in detail 3/A2.3 to comply with the requirements of Section 306.5, IMC 2006.
2. Show the size, routing, and termination of the condensate drain for FCU-1. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
3. Has power been provided to FCU-1? Reference: Section 3006, IBC 2006.
12/15/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the size of the "thru-wall drains" (scuppers) shown in detail 10/A2.3 to comply with the requirements of Section 1101.11.2.1, UPC 2006. Both scuppers appear to drain enough roof area to require a minimum width of 9.4".
2. Coordinate the water riser diagram 2/P4 with the plumbing plans on the 3rd floor (fixtures P3 and P4 are missing) and the 1st floor (one P1 is labeled as a P2). Reference: Section 103.2.3, UPC 2006.
12/16/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/24/2009 CPIERCE1 OUT TO CUSTOMER Completed
12/24/2009 CPIERCE1 REJECT SHELF Completed