Permit Number: T08CM00353
Parcel: 110034830

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM00353
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/13/2008 ROBERT SHERRY WATER REVIEW Approved
02/13/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/13/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/19/2008 RSHERRY1 WWM REVIEW Passed No new wastewater plumbing fixtures.
02/19/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET 2 OF 26
1. AT EXERCISE EQUIPMENT PAD "B", SHOW EXISTING CHAIN LINK FENCE TO BE REMOVED
2. SHOW SPOT GRADE ELEVATION OF NEW PATH, ACCESS TO PLAY GROUND EQUIPMENT AND TRANSITION TO EXISTING PATHWAYS.
3. SHOW SPOT ELEVATIONS OF RAMP FROM NEW PATHWAY TO NEW PLAY GROUND EQUIPMENT
4. SHOW ACCESSIBLE PATH TO EXISTING PLAYGROUND EQUIPMENT.
SHEET 3 OF 26
6.WHAT IS GRADE ELEVATION OF EXISTING BUILDING PATIO AT NEW RAMADA PATH CONNECTION
7. CAN THE CIRCULAR WALKWAY AROUND THE PARKING LOT BE CONNECTED TO THE WALKWAYS AT THE CURBS?
8. COORDINATE TABLES: NUMBER ONE HCP CAN NOT BE 0, SHOULD BE SOMEWHERE AROUND 2391.7
SHEET 4
9. DETAIL 1:
A. SHOULD CONCRETE ENTRANCE WAY BE FLUSH WITH NORTH ADJACENT CURB FOR ACCESS FROM THE NORTH? WHAT IS FINISH SURFACE OF AREA NORTH OF THIS CURB? LANDSCAPING?
B. IS ELEVATION 2393.3 SHOWN AT BEGINNING OF RAMP ENTRANCE A "TOP OF CURB" OR A "GUTTER" ELEVATION. IF IT IS A GUTTER ELEVATION, THEN THIS RAMP IS NOT NEEDED
10. SHOULDN'T AN ACCESSIBLE PATHWAY BE PROVIDED FROM THE EXISTING BUILDING TO THE CULTIVATION GARDEN?
11. THE DECOMPOSED GRANITE PATHWAY:
A. MAKE PATHWAYS 5' WIDE LIKE PATHWAYS AT RAMADA GARDEN OR PROVIDE A 5' TURN AROUND AT ALL INTSECTIONS AND CERTAIN LONG RUNS AND DEAD ENDS.
B. I'VE HAD TWO DIFFERENT READINGS FROM DIFFERENT PROFESSIONS ABOUT STABILIZED DECOMPOSED GRANITE BEING A SUITABLE MATERIAL ACCEPTABLE FOR ACCESSIBLE ROUTES. MY LANDSCAPE ARCHITECT ASSOCIATE SAYS IT WILL LOOSEN UP OVER A PERIOD OF TIME AND WILL NOT BE SUITABLE FOR WHEELCHAIRS. MY CHIEF INSPECTOR INDICATES THAT IT IS VERY SUITABLE AND WILL ONLY LOOSEN UP IF NOT CONTAINED ON EITHER SIDE BY A STEEL RIBBON OR A CONCRETE CURB. I WOULD LIKE TO HAVE A MANUFACTURER'S WARRANTY ON IT'S DURABILITY.
12. MAKE ALL PLANTERS AND COMPOST STALLS ACCESSIBLE, PROVIDE PATHWAY DIRECTLY UP TO SIDES OF EACH UNIT.
13. PROVIDE AN ACCESSIBLE ROUTE TO MIDDLE OF GARDEN AREA.
14. HAVE ALL SEATING ALONG PATHWAY 17"/19" HIGH
SHEET 6 OF 26
15. DETAIL 1:
A. PROVIDE SPOT GRADES OF ALL ACCESSIBLE ELEMENTS; WALKWAYS, EXSITING GRADES AND ACCESSIBLE PLAY GROUND EQUIPMENT ELEMENTS.
B. WRONG SCALE
C. SOME DIMENSIONS ARE INACCURATE
16. THE LONG CONCRETE WALKWAY IS NOT ACTUALLY A RAMP. IT IS LESS THAN 1/20 SLOPE. THE HANDRAIL SHOWN SHOULD PROBABLY BE A GARDRAIL TO PROTECT ONE FROM FALLING OFF AND NEEDS TO ADHERE TO ADAAG FIGURE 17, "VERTICAL GUARD RAIL"
SHEET 8 OF 26
17. DETAIL 8: PROVIDE 3' CLEAR BETWEEN RAILS
18. DETAIL 9: MAKE 17"/19" HIGH AT RIDGE
SHEET 10 OF 26
19. DETAILS 4 AND 5: NEITHER HANDRAIL DETAIL PROVIDES FOR A GUARD FROM FALLING THROUGH RAIL SUCH AS CALLED FOR IN ADAAG FIGURE 17, A 2" HIGH CURB, EXTENDED PLATFORMS OR A VERTICAL GUARDRAIL.
SHEET 17 OF 26
20. DETAIL A1, PROVIDE A MARKED ACCESSIBLE SPACE WITH AN ATENDANT SEATING BESIDE.
GENERAL:
21. NEED STRUCTURAL CALCULATIONS FOR DETAILS 8/8, A1/17, G1/17, D8/17, F8/17, B8/18, SHEETS 20, 21, 22 AND 23.
23. TYPICAL FOR ALL NEW PATWAYS; CROSS SLOPES NOT TO EXCEED 2% SLOPE, 1:50
24. ALL LETTERING TO BE MINIMUM OF 1/8"

Final Status

Task End Date Reviewer's Name Type of Review Description
02/19/2008 SUE REEVES OUT TO CUSTOMER Completed