Permit Number: T07CM04533
Parcel: 12407179C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM04533
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
12/05/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/05/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/05/2007 ROBERT SHERRY WATER REVIEW Approved
12/05/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/05/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/06/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM04533 12/5/07

1. Please remove the redundant #4 GROUND in conduit on Keynote 5 Sheet E4. Fourth wire will carry fault current back to the source. Reference NEC 250.24 (C).
2. Provide a circuit for the Garbage Disposal Keynote 9 Sheet E2.
12/06/2007 GERRY KOZIOL WWM REVIEW Approved
12/06/2007 MARTIN BROWN FIRE REVIEW Approved
12/11/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed