Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM04533
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/05/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
12/05/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
12/05/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
12/05/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/05/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/05/2007 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
12/06/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM04533 12/5/07 1. Please remove the redundant #4 GROUND in conduit on Keynote 5 Sheet E4. Fourth wire will carry fault current back to the source. Reference NEC 250.24 (C). 2. Provide a circuit for the Garbage Disposal Keynote 9 Sheet E2. |
12/06/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
12/06/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
12/11/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |