Permit Number: T07CM04447
Parcel: 13320129D

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM04447
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2007 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved GATE HEIGHT LOWERED FROM ORIGINAL SUBMITTAL FROM 7'2" TO 6'0"
11/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04447 11/26/07

1. If indeed this permit pertains to the gates and related equipment only, indicate as such on Sheet E1.2. It appears that we are looking at an entire site plan with primary, secondary, and services, but the Applicant indicates that this is on a separate permit.
2. Provide a disconnecting means for the gates per NEC Part IX.
3. Provide power requirements for the gates.
4. Demonstrate that the panel feeding the gates and lighting fixture is not overloaded.
5. Provide location of panels HPCI and HPDI.
6. Provide cut sheets for the lighting fixture.
7. Demonstrate compliance with the Tucson Lighting Code.
11/26/2007 PAUL MACHADO ENGINEERING REVIEW Approved
11/26/2007 DAVE MANN FIRE REVIEW Approved
11/26/2007 HEATHER THRALL ZONING REVIEW Approved
12/14/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/14/2007 CPIERCE1 APPROVAL SHELF Completed