Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM04447
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2007 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | GATE HEIGHT LOWERED FROM ORIGINAL SUBMITTAL FROM 7'2" TO 6'0" |
| 11/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM04447 11/26/07 1. If indeed this permit pertains to the gates and related equipment only, indicate as such on Sheet E1.2. It appears that we are looking at an entire site plan with primary, secondary, and services, but the Applicant indicates that this is on a separate permit. 2. Provide a disconnecting means for the gates per NEC Part IX. 3. Provide power requirements for the gates. 4. Demonstrate that the panel feeding the gates and lighting fixture is not overloaded. 5. Provide location of panels HPCI and HPDI. 6. Provide cut sheets for the lighting fixture. 7. Demonstrate compliance with the Tucson Lighting Code. |
| 11/26/2007 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 11/26/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/26/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 12/14/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/14/2007 | CPIERCE1 | APPROVAL SHELF | Completed |