Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/20/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04338 11/20/07

1. Panel designation is "L1" on the panel schedule, but the circuit designations on Sheet E1 are "L1", "L2", and "L3". Please clarify.
2. One the panel schedule, clearly indicate new receptacle loads. The only receptacle loads indicated are on the north, south, and front walls, so could not be a part of this project.
3. Account for ALL electrical loads on the panel schedule. For example, the load for one of the AC/Heaters is not indicated.
4. Add a demand factor of 25% for any continuous loads and for the largest motor, on the panel schedule.
5. Panel Schedule calls this a 20A panel. Sheet A4 refers to this as a 200A panel. Please clarify.
6. Put the job address on the sheet with the panel schedule.
7. Registrant shall apply seal to all plans. Reference Arizona Board of Technical Registration 32-125.