Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM04338
Parcel: 11007414C

Address:
3995 E GRANT RD

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM04338
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/20/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM04338 11/20/07

1. Panel designation is "L1" on the panel schedule, but the circuit designations on Sheet E1 are "L1", "L2", and "L3". Please clarify.
2. One the panel schedule, clearly indicate new receptacle loads. The only receptacle loads indicated are on the north, south, and front walls, so could not be a part of this project.
3. Account for ALL electrical loads on the panel schedule. For example, the load for one of the AC/Heaters is not indicated.
4. Add a demand factor of 25% for any continuous loads and for the largest motor, on the panel schedule.
5. Panel Schedule calls this a 20A panel. Sheet A4 refers to this as a 200A panel. Please clarify.
6. Put the job address on the sheet with the panel schedule.
7. Registrant shall apply seal to all plans. Reference Arizona Board of Technical Registration 32-125.