Permit Number: T07CM03927
Parcel: 12906470B

Address:
2619 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T07CM03927
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2008 STEVE SHIELDS ZONING REVIEW Approved
09/10/2008 ANDREW CONNOR LANDSCAPE REVIEW Approved
09/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/13/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: October 13, 2008
SUBJECT: Site Plan and Change of Use
TO: J.A.C.A. Design
LOCATION: 2619 E 22nd Street, T14S, R14E, Section 17, Ward 5
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07CM03927 (Third Review)


RESUBMITTAL REQUIRED: Site Plan and Drainage Statement

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan and drainage statement for the above referenced property. Engineering Division does not recommend approval of the site plan or drainage statement at this time. Please address the following review comments prior to the next submittal.

Site Plan:

1. It is difficult to know if the items have been addressed. Ensure that a response letter to the comments along with the corrected copies of the Site Plan is submitted with next review.
2. Complied
3. Complied
4. Complied
5. Complied
6. Complied
7. Complied
8. DS Sec.2-02.2.1.A.11 & DS Sec.3-01.3.2.C: Depict curb returns for MS&R and label 25-feet radii concrete curbs per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213) at the driveway entrance along 22nd Street. The curbs should be constructed at the edge of pavement OR get approval from Transportation Department.

Note that 18' Radius are required per transportation. Provide email or approval of proposed curb returns from transportation.

9. Revise the driveway location to meet the requirements per City of Tucson, Transportation Access Management Guidelines, Guideline 5.4.1 states entrance and exit drives crossing arterial and collectors are limited to two per three hundred feet of frontage along any major roadway. The nearest pavement edges spaced at least eighty feet apart. Guideline 5.4.1 states a minimum of one hundred and fifty feet, measured at curbline, shall separate the nearest pavement edge of any entrance or exit driveway and the curbline to any signalized intersection with arterial and collector roadways. Contact Jose Ortiz, Civil Engineer in regards to Transportation Management Guidelines. Provide approval letter from TDOT for driveway.
10. Complied.
11. See comments by Ron Brown for all handicap access comments.
12. Complied
13. Fully dimension loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14. Provide (label and dimension) the required onsite maneuvering area(s).

Explain why what is not required and provide documentation waiving requirement.
14. Complied
15. Complied
16. Complied.
17. Complied
18. Complied
19. No easements.
20. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.

Call out distances from centerline to curbs sidewalks, driveways, etc.

21. Provide contour interval on plan - preferably below the north arrow and scale.
22. Complied
23. Complied
24. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. Provide detail with dimensions for refuse container on the site plan, the enclosure must have a minimum inside clear dimension of 10 feet by 10 feet between steel bollards that are required between the container and the enclosure's rear and sidewalk. Refer to DS Sec.6-01.4.2 for specifications and requirements on access, placement of containers, bin enclosure and construction. For curbside pickup a letter of approval will be required from COT Environmental Services and a Development Standard Modification Request (DSMR) may be required prior to site plan approval. Detail was not provided in submittal please provide for review.

Per letter from Andy - add notes as required.

25. DS Sec.2-02.2.1.A.32: Label and show the maneuverability for refuse vehicles in plan view at the proposed refuse container location. Positioning of trash area should allow for 14' X 40' clear approach, show access dimensioning to proposed trash enclosure.
26. Note added.
27. Complied
28. Roof down spout locations for buildings at pedestrian circulation areas have been acknowledged. Provide detail for the dimension of the proposed scuppers that are used for collecting onsite roof drainage at all pedestrian sidewalks are required, refer to City of Tucson details. Any scuppers proposed under the sidewalk will be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk. Scupper needs to be provided just south of building so that flow under new sidewalk is established.
29. Complied
30. Complied
31. Complied
32. Handicap sign to specify $532.00 Fine and T.C.C. 20-222. Modify accordingly within detail.
33. Complied
34. Additional comments may be forthcoming depending on conditions.

Drainage Statement:

1. Include a response letter to the comments along with the corrected copies of the Drainage Statement.
2. The proposed Drainage Statement must provide a discussion with calculations for the proposed scuppers to ensure that scuppers contain the 10-year event under the sidewalks.
3. Identify the 100-year floodplain boundary per the City of Tucson Flood Hazard study performed by J.E. Fuller and Associates. Provide the date of the study along with the title of the report. In addition, provide information from the previous study including but not limited to a floodplain boundary map and an aerial photograph that shows the location of the property and all offsite/onsite floodplains to ensure that they do not affect the proposed building. Add floodplain boundary on site plan.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
10/23/2008 CPIERCE1 OUT TO CUSTOMER Completed
10/23/2008 SUE REEVES REJECT SHELF Completed