Permit Number: T07CM03771
Parcel: 12216115A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03771
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2007 VFLORES1 BUILDING-COMMERCIAL REVIEW Needs Review
09/25/2007 GERRY KOZIOL WWM REVIEW Approved
09/25/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/25/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm03771 9/25/07

1. Fault calculations allow wire length of 4/0 in Conduit 10 to be 55'. The most that appear to be allowable is 30' as scaled from Sheet E-1. Panels R and R1 appear to be rated less than the ACF.
2. If the intent is to series rate 55,000/10,000 this would imply a three tiered rating (MCB on R, Panel R1 100A CB, R1 branch CBs). Not available commercially.
3. Panel R schedule indicates "Fully Rated", in conflict with Note B Series Rating Notes.
4. Panel R1 schedule indicates "Series Rated 22K/10KAIC, inconflict with Note B Series Rating Notes.
5. Keyed Note 5 Sheet E-1 indicates "Existing Panel R." Line Diagram indicates that this is a new panel. Please clarify.
09/25/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved