Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03771
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/25/2007 | VFLORES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
09/25/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
09/25/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/25/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t07cm03771 9/25/07 1. Fault calculations allow wire length of 4/0 in Conduit 10 to be 55'. The most that appear to be allowable is 30' as scaled from Sheet E-1. Panels R and R1 appear to be rated less than the ACF. 2. If the intent is to series rate 55,000/10,000 this would imply a three tiered rating (MCB on R, Panel R1 100A CB, R1 branch CBs). Not available commercially. 3. Panel R schedule indicates "Fully Rated", in conflict with Note B Series Rating Notes. 4. Panel R1 schedule indicates "Series Rated 22K/10KAIC, inconflict with Note B Series Rating Notes. 5. Keyed Note 5 Sheet E-1 indicates "Existing Panel R." Line Diagram indicates that this is a new panel. Please clarify. |
09/25/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |